Boiler type Elite Fire Tube Combi (floor Mount)

Error code Er:61

Cause:

Fan Speed Feedback Signal Abnormal 

Solution:

This Error Code will go away when the condition is remedied. If Error happens again:
1. Check the connections to the fan. Ensure all are secure.
2. If the fan does not rotate during the ignition sequence, check for AC8V~26.5V power at the fan connection. If AC8V~26.5V power is present at the control, replace the fan. If the blower does not have AC8V~26.5V power, check power at the control. If AC8V~26.5V power is not present at the control, replace the control.
3. If the problem persists, replace the main control.