Boiler type Mod con 850

Error code F09

Cause:

No flame detected – Boiler will make three attempts at ignition before the control goes into this lockout condition.

Solution:

- Watch the igniter through the observation window provided.
- If there is no spark, check the spark electrode for the proper ¼” gap.
- Remove any corrosion from the spark electrode and flame rectifier probe.
- If there is a spark but no flame, check the gas supply to the boiler.
- If there is a flame, check the flame sensor.
- Check any flue blockage or condensate blocks.