Boiler type CL4-210(W)

Error code Err4

Cause:

Burner Output (B1) Fault

Solution:

B1 output sensed powered during safety output relay check sequence or un-powered during running, or powered in idle in combination with water temperature above 264°F limit. Cycle power to the control. Replace control if problem persists.