nl en de
Selecteer uw gewenste taal

In welk land bevindt uw cv ketel zich?

Storingen


Ketel type MPO-IQ147

Storingscode ErP9

Oorzaak:

No Ignition, Check Cad Cell

Oplossing:

The burner lit very late during the trial for ignition and is susceptible to not lighting.
-Check cad cell for proper alignment and clean if necessary.
-Check burner adjustments (refer to burner manufacturers instructions)
-Check electrodes and spring contacts (if equipped) and adjust per manufacturers  recommendations.
-Check if the pump is generating adequate pressure.
-Check the fuel supply lines and filter for obstructions.