nl en de
Selecteer uw gewenste taal

In welk land bevindt uw cv ketel zich?

Storingen


Ketel type MPO-IQ147

Storingscode ErP91

Oorzaak:

Communication Error

 

Oplossing:

Communications error has been detected.
Remove all devices from the Enviracom connections, 3-pin plug and screw terminals "1-2-3".    
If the error does not clear within one minute, measure the voltage on terminals "2" and "3".    
If the voltage across terminals "2" and "3" is between 20VAC and 30VAC, replace control.    
If it is outside of that range, review boiler wiring.  There should be approximately 24VAC across "2" and "3".